Operating temperature
|
|
|
0 … 55 °C
|
- Relative humidity at 25 °C
|
95%
|
|
≤ 10 K/h
|
Storage temperature
|
|
|
-40 … 70 °C
|
- Relative humidity at 25 °C
|
95%
|
|
≤ 20 K/h
|
Air pressure during operation
|
|
|
860 hPa (= 1500 m above sea-level) (reduced cooling performance at lower air pressure)
|
|
1080 hPa
|
Air pressure during storage
|
|
|
660 hPa (= 3500 m above sea-level)
|
|
1080 hPa
|
Ventilation
|
Separate or forced ventilation
|
Mechanical ambient conditions
|
Vibration during operation (stationary use)
|
IEC 60068-2-6 Test FC (10 cycles per axis)
|
|
0.075 mm amplitude
|
|
9.8 m/s2 (= 1 g constant acceleration)
|
Vibration during transport/storage (in delivery packaging)
|
IEC 60068-2-6 Test FC (10 cycles per axis)
|
|
3.5 mm amplitude
|
|
9.8 m/s2 (= 1 g constant acceleration)
|
Electromagnetic compatibility
(heating control is installed in control cabinet)
|
|
Radio interference suppression (emitted interference)
|
EN 55011 Class A, Group 1; 10 m measuring distance
|
Immunity to conducted interference (burst)
|
EN 61000-4-4
|
|
2 kV with switching network
|
- Signal lines that exit the device
|
2 kV with clamp
|
Immunity to conducted interference (HF‑irradiation)
|
EN 61000-4-6 10 V (0.15 to 80 MHz)
|
Immunity to static electricity discharges (ESD) (only tested on the frame)
|
EN 61000-4-2
|
|
4 kV
|
|
8 kV
|
Immunity to high-frequency emmission
|
EN 61000-4-3 or EN 50204 10 V/m (80 … 1000 MHz) 10 V/m pulse modulated (900 ± 5 MHz)
|
Immunity to high-energy pulses (surge)
|
EN 61000-4-5
|
|
|
|
1 kV
|
|
2 kV
|
|
|
|
1 kV
|