Climatic conditions
|
|
Operating temperature
|
|
|
0 °C ... 55 °C
|
- Relative humidity at 25 °C
|
95 %
|
|
10 K/h
|
Storage temperature
|
|
|
-40 °C ... 70 °C
|
- Relative humidity at 25 °C
|
95 %
|
|
20 K/h
|
Atmospheric pressure during operation
|
|
|
860 hPa (= 1500 m above msl) (limited cooling performance at lower atmospheric pressure)
|
|
1080 hPa
|
Atmospheric pressure during storage
|
|
|
660 hPa (= 3500 m above msl)
|
|
1080 hPa
|
Ventilation
|
Self-ventilation or forced ventilation
|
Mechanical conditions
|
|
Vibrations during operation (stationary use)
|
IEC 60068‑2‑6 test FC (10 cycles per axis)
|
|
0.075 m amplitude
|
|
9.8 m/s2 (= 1 g constant acceleration)
|
Vibrations during transport/storage (in shipping packaging)
|
IEC 60068‑2‑6 test FC (10 cycles per axis)
|
|
3.5 mm amplitude
|
|
9.8 m/s2 (= 1 g constant acceleration)
|
Shock during operation (stationary use)
|
IEC 60068‑2‑27 test EA 150 m/s2 [15 g, half-sine] duration 11 ms 3 shocks per axis and direction
|
Shock during transport/storage (in shipping packaging)
|
IEC 60068‑2‑29 test EB 250 m/s2 [25 g, half-sine] duration 6 ms 1000 shocks per axis and direction
|
Electromagnetic compatibility
|
|
RI suppression (emitted interference)
|
Limit class A to EN 55011 group 1
|
Noise immunity to conductive interferences (burst)
|
To EN 61000‑4‑4
|
|
2 kV with switching network
|
- Signal lines which leave the unit
|
2 kV with clip-on coupling device
|
Noise immunity to conductive interferences (RF injection)
|
To EN 61000‑4‑6 10 V (0.15 MHz ... 80 MHz)
|
Noise immunity to discharging of static electricity (ESD)
|
To EN 61000‑4‑2
|
|
4 kV
|
|
8 kV
|
Noise immunity to RF irradiation
|
EN 61000‑4‑3 or ENV 50204 10 V/m (80 MHz to 1000 MHz) 10 V/m pulse-modulated (900 ”5 MHz)
|
Noise immunity to high-energy pulses (surge)
|
To EN 61000‑4‑5
|
Power supply lines
|
|
|
1 kV
|
|
2 kV
|
PROFIBUS line
|
|
|
1 kV
|