Outputs per power output (LA 724i HP)
|
12
|
Electrical isolation from control unit
|
By opto-triac and optocoupler specified according to VDE 0884
|
Insulation voltage
|
|
|
5 kV
|
|
5.3 kV
|
Electrical isolation between power outputs
|
No
|
Load voltage (for star and delta connections)
|
|
|
230 V AC / 400 V AC
|
|
187 V ... 264 V / 340 V ... 460 V (TN system)
|
|
50 Hz/60 Hz (47 Hz ... 63 Hz)
|
Total current per phase and module
|
Max. 40 A
|
Current per busbar
|
Max. 120 A
|
Output voltage
|
Full waves or half-waves switched at zero crossover
|
Output current
|
|
|
10 A
|
|
Max. 7 mA
|
Power loss
|
Typ. PV = 0.7 W/A x I + 0.16 W/A2 x I2 (I = control current in the channel)
|
Switching capacity (simultaneity 100 %)
|
2300 W per channel at 230 V
4000 W per channel at 400 V
Note: the total current per phase of 40 A must not be exceeded. Min. 75 W per channel
|
Parallel connection of heat emitters to one channel
|
|
|
Typ. 5
|
- Minimum power per heat emitter
|
200 W
|
Total switching capacity per LA 724i HP (ambient temperature = 40 °C)
|
|
- Without forced ventilation
|
13 kW
|
|
21 kW
|
Type of load
|
Resistive loads with max. 15 times the cold current in the 1st half-wave (if necessary, flash heat emitters can be measured at Siemens)
|
Overload
|
5 times the rated current for 20 ms
|
Thermal protection
|
Yes, by NTC thermistor 92 °C ± 3 °C: warning to host controller via PROFIBUS DP
100 °C ± 3 °C: switching off of power outputs
|
Short-circuit protection
|
One 10 A/250 V quick-blow fuse per output
|
Overvoltage protection
|
By Transil diodes
|
Connection line
|
R
max = 14 W (short-circuit protection is thus ensured)
|
Dimensions of LA 724i HP (W x H x D)
|
50 mm x 480 mm x 210 mm
|
Weight, approx.
|
5.3 kg
|